ASHRAE Guideline 36

High-Performance HVAC Sequences. Built to the Standard.

ASHRAE Guideline 36 defines optimized, standardized sequences of operation for commercial HVAC systems. Field-tested across building types, G36 reduces HVAC energy use by an average of 30% — without replacing any equipment.

~30%
Average HVAC energy reduction vs. conventional sequences
Lawrence Berkeley National Laboratory field studies
2–7 yr
Typical simple payback, including rebate offsets
Field demonstration data
G36-2024
Current edition — 23 addenda incorporated, updated AFDD and humidity sequences
ASHRAE 2024

The Standard

What Is ASHRAE Guideline 36?

Published by ASHRAE, Guideline 36 is a library of standardized, high-performance sequences of operation for common commercial HVAC systems — VAV terminal units, multi-zone air handling units, cooling plants, heating plants, and more.

Traditional HVAC programming is often built from scratch on each project — with custom logic that varies by programmer, platform, and contractor. The result is sequences that work at startup but drift over time, aren't auditable, and can't be maintained by anyone other than whoever wrote them.

G36 replaces that with a documented, peer-reviewed standard. The sequences are published, the commissioning checklists follow from the spec, and any qualified controls engineer can read and maintain the logic — regardless of who installed it.

Current Edition
Guideline 36-2024

The 2024 edition incorporates 23 addenda from prior versions, adding updated humidity-limiting strategies, outdoor air pollution modes, and enhanced AFDD sequences. California's Title 24 now references G36 requirements, and similar language is appearing in draft energy codes nationwide.

Who It Applies To
New Construction & Existing Buildings

G36 sequences apply to both new BAS installations and retrocommissioning projects. For existing buildings with VAV systems and modern BAS platforms, G36 implementation is often a reprogramming project — no equipment replacement required.

Open Standard
Platform-Agnostic by Design

G36 is not tied to any manufacturer or BAS platform. The sequences can be implemented on Niagara, Automated Logic, Johnson Controls Facility Explorer, or any platform that supports the underlying control logic — giving owners flexibility to choose their integrator.

What We Implement

G36 Sequences MJI Programs

Each sequence is implemented to spec, commissioned against Guideline 36 checklists, and handed back with full documentation.

Sequence 01

VAV Terminal Units

Dual-maximum control logic for VAV boxes with reheat — heating and cooling setpoints independently managed, deadband minimized, reheat locked out during economizer operation.

Typical Impact

Eliminates simultaneous heating and cooling; typically 15–25% AHU energy reduction.

Sequence 02

Multi-Zone AHUs

Supply air temperature reset, static pressure reset via trim-and-respond, and minimum outdoor air control per zone ventilation demand — all per Guideline 36 specs.

Typical Impact

Reduces fan energy, eliminates over-ventilation, and cuts reheat energy waste.

Sequence 03

Economizer Control

Differential dry-bulb or enthalpy economizer sequences with integrated demand-controlled ventilation. Outdoor air is maximized when conditions allow, throttled when not.

Typical Impact

Maximizes free cooling hours; prevents economizer faults that often go undetected for years.

Sequence 04

Chilled Water & Hot Water Plants

Chiller staging, chilled water supply temperature reset, variable primary flow, and boiler sequencing — all coordinated through the BAS rather than local controls.

Typical Impact

Plant efficiency improvements of 10–20% beyond code-minimum sequences.

Sequence 05

Automated Fault Detection & Diagnostics (AFDD)

Guideline 36 includes built-in AFDD algorithms for AHUs and terminal units. Faults like stuck dampers, failed actuators, and sensor drift are flagged automatically.

Typical Impact

Catches issues weeks before they affect occupant comfort or show up on an energy bill.

Why It Matters

Six Reasons to Upgrade to G36

Open Standard, No Lock-In

G36 sequences are published, documented, and platform-agnostic. Any qualified controls contractor can read, maintain, and extend the logic — your building's sequences aren't a black box owned by one vendor.

~30% Average HVAC Energy Savings

Field demonstrations across climate zones show an average of 31% HVAC energy reduction versus conventional sequences. Some implementations have reached 60%+ depending on baseline conditions.

Reduces Commissioning Time

Because the sequences are standardized and pre-validated, commissioning checklists follow a known structure. Less time debugging custom logic; more time verifying actual performance.

Built-In Fault Detection

G36 includes AFDD algorithms as part of the spec — not bolted on after the fact. Faults are detected at the sequence level, not just from alarm thresholds.

Supports LL97 Compliance

NYC buildings facing Local Law 97 exposure can use G36 implementation as a documented energy reduction measure. The savings are measurable, verifiable, and produce the data LL97 annual reporting requires.

Qualifies for Rebates

Verifiable kWh reductions from G36 sequences qualify under PSEG Long Island and NYSERDA rebate programs. MJI produces the engineering documentation these programs require.

Compatible Platforms

G36 Runs on the Platform You Already Have

Guideline 36 is not a hardware upgrade — it's a programming upgrade. If your BAS supports modern DDC programming, MJI can implement G36 sequences without replacing controllers or field devices.

Niagara N4 (Tridium)
MJI is N4 certified. G36 modules can be implemented natively in Niagara.
Johnson Controls Facility Explorer
G36 logic on JCI FX hardware. MJI is a JCI Authorized System Integrator.
BACnet Open Front Ends
G36 sequences exposed via BACnet — compatible with third-party monitoring and reporting platforms.
Is Your Building G36-Ready?
Do you have VAV terminal units?
G36 terminal unit sequences are likely directly applicable.
Do you have a modern BAS (Niagara, ALC, JCI FX, or similar)?
G36 sequences can be programmed without hardware replacement.
Is your building 5+ years post-commissioning?
Sequences have almost certainly drifted. G36 re-implementation resets performance to an optimized baseline.
Are you tracking LL97 or seeking PSEG/NYSERDA rebates?
G36 savings are measurable and documentable — exactly what compliance reporting and rebate applications require.
LL97 Compliance

G36 Produces the Documentation LL97 Requires

NYC buildings facing Local Law 97 exposure need measurable, verifiable energy reductions. G36 sequences produce trend data, fault logs, and energy benchmarks that support annual LL97 reporting — and demonstrate controls-based compliance strategies to auditors.

Learn about LL97 →
PSEG LI & NYSERDA Rebates

Verifiable kWh Savings Qualify for Rebates

PSEG Long Island and NYSERDA rebate programs pay per kilowatt-hour saved. G36 implementation produces the projected and measured savings documentation these programs require to approve applications — and MJI handles the paperwork.

Explore LI rebate programs →
MJI Custom Programming

G36 Is One Part of a Broader Programming Capability

G36 sequences are our preferred baseline for VAV systems and AHUs — but we also write custom ladder logic, structured text, and site-specific sequences when the application demands it. One team covers the full programming scope.

See all programming services →
Indoor Air Quality

G36 Ventilation Sequences Support Full IAQ Monitoring

G36 DCV sequences regulate outdoor air via CO₂ — the foundation of ASHRAE 62.1 compliance. Pair G36 programming with MJI's IAQ monitoring service for full visibility into PM2.5, TVOC, CO, and humidity across every zone.

See IAQ monitoring →

Ready to Upgrade Your Sequences?

Tell us about your building — platform, system type, and what you're trying to achieve. We'll scope a G36 implementation and walk you through what the savings and rebate potential looks like.

Request a Proposal →