ASHRAE Standard 62.1

Ventilate to Occupancy, Not to Assumption.

ASHRAE Standard 62.1 is the ventilation standard referenced by the NYC Mechanical Code for all commercial buildings. Its demand control ventilation (DCV) provisions let a properly programmed BAS scale outdoor air delivery to actual occupancy — reducing heating and cooling energy 9–33% versus fixed outdoor air systems.

MJI Energy programs 62.1-compliant DCV sequences, handles sensor placement and commissioning, and produces the documentation NYC DOB and rebate programs require.

9–33%
HVAC energy reduction from CO2-based DCV vs. fixed OA systems
ASHRAE Research Project RP-1747
62.1-2022
Current edition — mandatory prerequisite for LEED v5 BD+C projects
ASHRAE / USGBC
±75 ppm
Required CO2 sensor accuracy at 1,000 ppm per ASHRAE 62.1-2022 Section 6.2.6.1.3
ANSI/ASHRAE 62.1-2022

The Standard

What Is ASHRAE Standard 62.1?

ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality, sets minimum outdoor air delivery rates and system requirements for commercial buildings — offices, retail, restaurants, schools, hotels, and healthcare outpatient facilities. First issued in 1973 and updated on a three-year cycle, the current version is 62.1-2022.

The standard has been adopted by reference into the International Mechanical Code (IMC), which forms the basis of the NYC Mechanical Code. For commercial buildings in New York City, 62.1 compliance is legally required — not optional.

Its demand control ventilation provisions allow a BAS to modulate outdoor air based on CO2 sensor readings — ensuring every occupied zone is properly ventilated based on who is actually there, not worst-case design assumptions.

Minimum Ventilation Formula
Voz = (Rp × Pz) + (Ra × Az)

The two-component formula separates people-based OA (scales with occupancy, addressed by DCV) from area-based OA (addresses building materials off-gassing — cannot go to zero even when unoccupied). A typical office requires 5 CFM per person plus 0.06 CFM per sq ft.

DCV Mandate — ASHRAE 90.1
Required for High-Occupancy Spaces

Energy code companion ASHRAE 90.1-2019 Section 6.4.3.8 makes DCV mandatory for spaces over 500 sq ft with design occupancy ≥ 25 people/1,000 sq ft and an economizer or >3,000 CFM design OA. Conference rooms, lobbies, restaurants, and large open offices typically qualify.

CO2 as an Occupancy Proxy
A Ventilation Tool, Not a Safety Alarm

ASHRAE explicitly defines CO2 concentration as a proxy for ventilation adequacy — not a direct health hazard indicator. Rising CO2 signals insufficient dilution relative to occupancy. A full IAQ monitoring system also covers PM2.5, VOCs, and CO (a direct safety concern) independent of DCV.

How It Works

DCV: What MJI Programs and Commissions

Each DCV installation follows a documented process — from sensor placement through commissioning and NYC DOB documentation.

01
CO2 Sensor Placement
Sensors are positioned in the breathing zone — not near supply diffusers or return grilles — in representative locations per each ventilation zone. Placement strategy is documented and submitted for commissioning.
02
BAS Programming
CO2 readings are integrated into AHU and VAV controllers to modulate outdoor air damper position proportionally. Cmax setpoints are established per ASHRAE 62.1 for each space type — typically 1,000 ppm for commercial occupancies.
03
Fail-Safe Logic
Per ASHRAE 62.1 Section 6.2.6.1.3, the system must revert to full design outdoor air delivery on sensor fault. MJI programs and verifies this fail-safe behavior as part of every DCV installation.
04
Commissioning & Documentation
NYC DOB requires documentation for DCV systems in assembly occupancies over 500 sq ft. MJI handles the commissioning record, sequence of operations documentation, and supports any required inspection.

Why It Matters

Six Reasons to Implement DCV

Required by Energy Code

ASHRAE 90.1-2019 Section 6.4.3.8 makes DCV mandatory for spaces over 500 sq ft with design occupancy ≥ 25 people per 1,000 sq ft and an air economizer or >3,000 CFM design outdoor airflow. Most VAV systems in commercial buildings qualify.

9–33% HVAC Energy Savings

CO2-based DCV reduces HVAC energy consumption by 9–33% compared to constant-volume outdoor air systems, per ASHRAE Research Project RP-1747. Savings come from reduced heating, cooling, dehumidification, and fan energy on every occupied day.

Scales to Actual Occupancy

Most commercial buildings operate at 30–60% of peak occupancy on a typical day. A fixed outdoor air system conditions for worst-case assumptions all day long. DCV delivers only what's needed — in real time.

Supports LL97 Compliance

For NYC buildings facing Local Law 97 carbon penalties, reducing HVAC energy directly cuts CO2e emissions. DCV is one of the few controls-only strategies that produces measurable, documentable reductions without equipment replacement.

Open Standard, Any Platform

ASHRAE 62.1 DCV sequences are not tied to any manufacturer. MJI programs them on Niagara N4, Johnson Controls Facility Explorer, and any BAS platform that supports modern DDC programming — no new hardware required in most cases.

LEED & WELL Alignment

LEED v5 requires ASHRAE 62.1-2022 compliance as a mandatory prerequisite. WELL Building Standard v2 Option 4 awards credit for demonstrating CO2 levels at or below 900 ppm in occupied spaces — both are supported by proper DCV implementation.

Related Pages

Ready to Ventilate Smarter?

Tell us about your building — platform, system type, and occupancy profile. We'll scope a DCV implementation and walk you through the energy savings and rebate potential.

Request a Proposal →